BE AWARE OF LEAD-BASED PAINT HAZARDS: Many residences built before 1978 have paint that contains lead, which can pose a serious health hazard if paint, chips, and dust are not handled properly. See the U.S. Environmental Protection Agency (EPA) lead brief before disturbing painted surfaces in homes of this vintage. Follow the HUD “Lead-Safe Housing Rule” for requirements for notification, evaluation and reduction of lead-based paint hazards.
BE AWARE OF ASBESTOS HAZARDS: Homes older than 1977 may have building products that contain asbestos such as insulation, high-temperature gaskets, roofing and siding shingles, and vinyl sheet flooring. See the EPA asbestos brief before disturbing such materials.
BE AWARE OF MOLD AND MOISTURE HAZARDS: Molds can gradually destroy materials they grow on; can irritate the eyes, skin, nose, throat, and lungs of both mold-allergic and non-allergic people; can cause asthma attacks in people with asthma who are allergic to mold; and can cause other serious health problems. To learn more about preventing and cleaning up mold in homes, see these mold guides and the EPA brief on What to Wear When Cleaning Moldy Areas.
|
|
|
H1. Install Vent Dampers
Description
All
oil and gas furnaces and boilers have a vent (flue or chimney) to
discharge unwanted combustion gases to the outside. A vent damper
is a device installed in the vent of a furnace or boiler that automatically
closes the vent when the burner goes off to reduce the loss of warm
air up the chimney. Vent dampers save money by reducing the amount
of heat loss through the chimney during this off cycle. (Note: Codes
do not allow flue dampers--that is, dampers installed upstream of
the draft diverter or barometric damper--as a retrofit, although
flue dampers can be installed on some appliances at the time of
manufacture. Unlike flue dampers, vent dampers are installed downstream
of the draft diverter.)
The
level of savings from a vent damper depends on several factors.
In general, savings tend to be higher with larger, older, oversized
boilers because their off-cycle losses are greater. Savings also
depend on the absence of alternate escape routes for the hot air,
such as out a crevice in the basement or up a neighboring water
heater vent. If the hot air finds its way out of the building despite
the vent damper, savings will be lower.
Applicability
- Single-family
and multifamily buildings
-
Oil- or gas-fired boilers or furnaces with atmospheric burners
without vent dampers or flue dampers
Types
Considerations
-
Before a vent damper is installed on a gas boiler or furnace,
a PHA should make sure that the burner has an electronic ignition.
Installing a vent damper on a system with a standing pilot light
may cause safety concerns.
-
The vent damper should include a control that prevents the boiler
or furnace from operating when the vent damper is in the closed
position.
-
Contractors must be certified to install vent dampers.
Performance/Economics
-
Leak tight mechanical dampers are most effective.
-
Thermal vent dampers are not recommended since they do not allow
accurate timing.
-
Vent dampers reduce heating costs by approximately 5 to 8 percent.
Resources/Links
Energy Conservation for Housing
A Workbook, HUD, September 1998. Pages 7-37 through 7-39
address air infiltration and leakage.
Improving
Energy Efficiency in Apartment Buildings, American Council
for an Energy-Efficient Economy, 1995. ISBN 0-918249-23-6.Pages
98 through 103 address infiltration and air leakage measures in
apartment buildings.
Consumer
Guide to Home Energy Savings, American Council for an Energy
Efficient Economy, 1999, ISBN 0-918249-38-4. Pages 11 through 17
address strategies to control air leakage.
Insulation and Air Sealing. Part of the U.S. Department of Energy's Consumer's Guide. Discusses both air leakage and moisture control.
|